• General Specifications   Voltage AC (Un) 230V Voltage Range  176~276V AC Base Current (Ib)   10A Max. Current (Imax) 100A Mini Current (Imin)  0.5A Starting current  0.4% of Ib Power consumption  &lt;2W/10VA Frequency   50/60Hz(±10%) AC voltage withstand  4KV for 1 minute Impulse voltage withstand  6KV-1.2uS wavform Overcurrent withstand  30Imax for 0.01s Pulse output rate  1000imp/kWh (Import)   1000imp/kWh (Export) Display  LCD with blue backlit Max. Reading  99999.9kWh     Accuracy   Voltage 0.5% of range maximum Current 0.5% of nominal Frequency   0.2% of mid-frequency Power factor 1% of Unity Active power   1% of range maximum Reactive power   1% of range maximum Apparent power  1% of range maximum Active energy  Class 1 IEC62053-21   Class B EN50470-3 Reactive energy  1% of range maximum     Environment    Operating temperature   -25℃ to + 55℃ Storage and transportation temperature  -40℃ to +70℃ Reference temperature 23℃±2℃ Relative humidity   0 to 95%, non-condensing Altitude  up to 2500m Warm up time  10s Mechanical Environment M1 Electromagnetic environment E2 Degree of pollution  2 Output   Pulse OutputThe meter provides two pulse outputs. Both pulse outputs are passive type.Pulse 1:Export active energy, constant 1000imp/KWh, pulse width 100ms, non-configurablePulse 2:Import active energy, constant 1000imp/KWh, pulse width 100ms, non-configurable<br/> MechanicsDin rail dimensions   36x99x63 (WxHxD) DIN 43880 Mounting  DIN rail 35mm Sealing   IP51 (indoor) Material Self-extinguishing UL94V-0
    Product informatie

    General Specifications  
    Voltage AC (Un) 230V
    Voltage Range  176~276V AC
    Base Current (Ib)   10A
    Max. Current (Imax) 100A
    Mini Current (Imin)  0.5A
    Starting current  0.4% of Ib
    Power consumption  <2W/10VA
    Frequency   50/60Hz(±10%)
    AC voltage withstand  4KV for 1 minute
    Impulse voltage withstand  6KV-1.2uS wavform
    Overcurrent withstand  30Imax for 0.01s
    Pulse output rate  1000imp/kWh (Import)
      1000imp/kWh (Export)
    Display  LCD with blue backlit
    Max. Reading  99999.9kWh
       
    Accuracy  
    Voltage 0.5% of range maximum
    Current 0.5% of nominal
    Frequency   0.2% of mid-frequency
    Power factor 1% of Unity
    Active power   1% of range maximum
    Reactive power   1% of range maximum
    Apparent power  1% of range maximum
    Active energy  Class 1 IEC62053-21
      Class B EN50470-3
    Reactive energy  1% of range maximum
       
    Environment   
    Operating temperature   -25℃ to + 55℃
    Storage and transportation temperature  -40℃ to +70℃
    Reference temperature 23℃±2℃
    Relative humidity   0 to 95%, non-condensing
    Altitude  up to 2500m
    Warm up time  10s
    Mechanical Environment M1
    Electromagnetic environment E2
    Degree of pollution  2
    Output


     

    Pulse Output
    The meter provides two pulse outputs. Both pulse outputs are passive type.
    Pulse 1:Export active energy, constant 1000imp/KWh, pulse width 100ms, non-configurable
    Pulse 2:Import active energy, constant 1000imp/KWh, pulse width 100ms, non-configurable



    Mechanics
    Din rail dimensions  
    36x99x63 (WxHxD) DIN 43880
    Mounting  DIN rail 35mm
    Sealing   IP51 (indoor)
    Material Self-extinguishing UL94V-0


Categorie: kWh-meter
Artikelnummer: 254-SDM230DRRes


VOIT10208